How To Test Cable Insulation Resistance Using A Megger
Cable world logo

No results Found

Cable world logo

How to test cable insulation resistance (megger test) - step by step

Testing cable insulation resistance helps confirm that electrical systems stay safe and reliable under load. A megger test measures how well a cable’s insulation resists current leakage, showing whether it can handle voltage without breaking down. By applying a controlled DC voltage and reading the resistance, technicians can detect early signs of damage or moisture that may lead to faults or failures.

This simple yet vital test prevents costly downtime and ensures cables meet safety standards before energising a circuit. Knowing how to perform it correctly-setting the right voltage, connecting leads properly, and interpreting results-builds confidence in the system’s performance and safety.

Understanding each step of the megger test process makes it easier to identify problems, maintain equipment, and extend the lifespan of electrical installations.

Key Takeaways

What Is an Insulation Resistance Test?

An insulation resistance test measures how effectively an electrical system’s insulation prevents current from leaking between conductors or to earth. It checks the condition of insulation materials in cables, motors, transformers, and other equipment to ensure safe and efficient operation.

Why Insulation Testing Is Important

Insulation resistance testing helps identify faults before they cause electrical failures. Over time, insulation materials can degrade due to heat, moisture, vibration, or contamination. These factors reduce resistance and allow leakage current to flow, which can lead to shocks, short circuits, or fires.

A megohmmeter (often called a megger) applies a controlled DC voltage to measure resistance in megaohms (MΩ). High resistance values indicate good insulation integrity, while low values signal possible deterioration or damage.

Routine testing supports preventive maintenance. By tracking resistance over time, technicians can detect gradual insulation breakdown and act before it affects system reliability. In industrial settings, this reduces downtime and helps maintain compliance with safety and performance standards.

Condition of InsulationTypical Resistance (MΩ)Action Required
Excellent>100None
Acceptable10–100Monitor
Marginal1–10Investigate
Poor<1Repair/Replace

When to Carry Out a Megger Test

Technicians perform insulation resistance tests at several key stages. Before installation, testing verifies that new cables or equipment are free from manufacturing defects or moisture. After installation, it confirms that no damage occurred during handling or connection.

Regular testing during scheduled maintenance ensures continued insulation integrity, especially in harsh or high-voltage environments. Equipment such as transformers, switchgear, and motors should be checked periodically to detect early signs of insulation ageing.

Testing is also essential after repairs or exposure to adverse conditions, such as flooding or overheating. Consistent record-keeping allows comparison of new readings with previous results to identify trends and plan corrective actions early.

UK Standards and Safety Guidance

In the United Kingdom, insulation resistance testing follows recognised IEC and BS standards, such as IEC 60364, BS 7671 (IET Wiring Regulations), and IEEE 43 for rotating machines. These standards define test voltages, acceptable resistance values, and safety procedures.

Testing must only be carried out on de-energised circuits using proper lockout/tagout methods. Personnel should wear insulated gloves, safety glasses, and arc-rated clothing to protect against electrical hazards.

The Health and Safety Executive (HSE) advises that only trained individuals perform these tests. Following manufacturer instructions and national standards ensures accurate results and prevents equipment damage. Compliance with these guidelines helps maintain electrical safety and extends the service life of insulation materials.

Tools and Safety Preparation

Accurate insulation resistance testing depends on using the correct tools, wearing proper protective gear, and preparing cables carefully. Each step prevents false readings and reduces the risk of electrical shock or equipment damage.

Required Test Equipment

A megger or insulation resistance tester applies a controlled DC voltage to measure insulation quality in megohms (MΩ). Common test voltages range from 250 V to 1000 V for low-voltage systems, and up to 5000 V for high-voltage cables.

Essential equipment includes:

Technicians should check the tester’s battery level and verify that the instrument reads zero when shorted. Damaged or worn megger test leads can cause erratic readings, so they must be inspected before use.

A clean, dry work area helps maintain consistent readings. Moisture or dust on terminals can lower resistance values and lead to misinterpretation of results.

PPE and Safe Isolation Steps

Only authorised personnel should perform a megger test. The test involves high DC voltage, so strict safety precautions are essential.

Required personal protective equipment (PPE) includes:

Before testing, they must de-energise the circuit and verify it is isolated using a voltage detector. Lockout and tagout procedures prevent accidental energisation.

All nearby equipment should be grounded, and the earth point must be secure. The operator should keep one hand away from metal surfaces to reduce the risk of a current path through the body.

After testing, discharge the cable by shorting conductors to earth to safely remove any stored charge.

Preparing Cables for Testing

Proper cable preparation ensures accurate results and protects the insulation. The cable ends should be clean, dry, and free from grease or moisture.

Technicians should strip insulation carefully to expose conductors without nicking them. Connect the megger test leads-one to the conductor and the other to the earth point or metallic sheath.

If multiple cores exist, test each separately to identify insulation breakdown between conductors. For long or stored cables, allow them to stabilise at ambient temperature before testing, as humidity and temperature affect resistance readings.

Record the cable identification, test voltage, and measured resistance in a log sheet. Documenting results helps track insulation condition over time and detect gradual deterioration.

Setting the Correct Test Voltage

Selecting the correct test voltage ensures accurate insulation resistance readings and prevents damage to the cable under test. The voltage must match the cable’s rated voltage and insulation type to avoid overstressing or under-testing the insulation.

Recommended Voltages for Different Circuits

Technicians should apply a test voltage that corresponds to the system’s rated voltage. Using too low a voltage can mask insulation faults, while too high a voltage may cause premature insulation breakdown.

For low-voltage circuits (up to 1 kV), the typical test voltage ranges from 250 V to 1000 V DC. Control and communication cables often use 250 V or 500 V.

For medium-voltage cables (1 kV to 33 kV), the test voltage usually ranges from 1000 V to 5000 V DC, depending on the cable’s design and insulation class. A 6.6 kV cable, for example, is often tested at around 3.8 kV between conductor and earth and 6.6 kV between phases.

High-voltage systems above 33 kV may require even higher test voltages, often specified by manufacturer or industry standards such as IEEE 43 or IEC 60060.

Cable TypeRated VoltageTypical Test Voltage (DC)
Control / Signal≤ 250 V250–500 V
Low Voltage Power0.6–1 kV500–1000 V
Medium Voltage3.3–11 kV2500–5000 V
High Voltage> 33 kV5000 V and above

Typical Minimum Resistance Values

The measured insulation resistance should meet or exceed the minimum acceptable value for the cable type and voltage class. Readings below this level may indicate moisture, damage, or insulation deterioration.

For low-voltage circuits, a minimum of 1 MΩ per kV of operating voltage is a common rule of thumb. For instance, a 1 kV cable should show at least 1 MΩ.

Medium- and high-voltage cables often require much higher resistance, typically in the gigaohm (GΩ) range. A healthy 6.6 kV cable might show between 60 GΩ and 80 GΩ when tested at 3800–6600 V DC.

Environmental factors like humidity and temperature can affect readings, so technicians should record both conditions during testing. Using a guard terminal on the megger helps improve accuracy by isolating surface leakage currents from the true insulation resistance.

System VoltageMinimum Acceptable Resistance
Up to 1 kV≥ 1 MΩ
1–33 kV≥ 100 MΩ
Above 33 kV≥ 1 GΩ

Step-by-Step: How to Perform a Megger Test

Accurate insulation resistance testing depends on safe preparation, correct instrument setup, and careful measurement. Each stage ensures the cable and connected equipment remain protected while producing reliable readings that reflect the true condition of the insulation.

Disconnect Power and Isolate the Circuit

Before testing, the technician must de-energise the circuit completely. This prevents accidental shock and avoids damage to the megger or cable. All power sources, including backup feeds, must be switched off and locked out according to site safety rules.

Next, disconnect the cable from connected equipment such as motors, control panels, or junction boxes. This isolation ensures the test measures only the insulation resistance of the cable itself. Leaving other devices connected can distort readings or cause false results.

Use a voltage detector to confirm the circuit is dead. Even residual voltage can affect the test. After confirming isolation, label or tag the cable ends to prevent accidental reconnection during the test. Proper isolation protects both personnel and equipment.

Connect the Megger to the Conductors

Once the circuit is safe, prepare the megger test leads. Inspect the leads for damage and ensure they are clean and dry. Connect one lead to the conductor or group of conductors being tested and the other lead to the cable’s metallic sheath or earth.

For multi-core cables, test each core separately. This helps identify faults between conductors or between a conductor and earth. The table below shows typical connection setups:

Test TypeLead 1 ConnectionLead 2 Connection
Core to EarthIndividual conductorCable sheath or armour
Core to CoreOne conductorAdjacent conductor

Keep all connections tight and stable. Loose or dirty contacts can cause fluctuating readings. The megger must remain off until all connections are confirmed secure.

Apply Test Voltage and Take Readings

Set the megger test voltage according to the cable’s rating. Common test voltages include 250 V, 500 V, or 1000 V DC. For high-voltage cables, higher test levels may apply. Always follow the manufacturer’s recommendations.

Press the test button and maintain the voltage for about one minute. During this time, the meter measures insulation resistance in megohms (MΩ). A high resistance value, usually above 20 MΩ, indicates good insulation. Low or unstable readings may point to moisture, dirt, or insulation breakdown.

Observe the reading carefully. If the value drops rapidly, stop the test and inspect the cable. Record both the voltage used and the final resistance value for reference.

Discharge and Record Results

After testing, the cable may hold a residual charge. Use the megger’s discharge function or manually short the conductors to earth for a few seconds to safely release stored energy. Never touch the cable before confirming it is fully discharged.

Once safe, disconnect the test leads in reverse order. Check that all connections are clean and undamaged before returning the system to service.

Record the results in a log or inspection form. Include details such as cable identification, test voltage, measured resistance, date, and technician name. Consistent documentation helps track insulation performance over time and supports preventive maintenance planning.

How to Read and Record Results

Accurate readings help confirm the condition of cable insulation and ensure electrical systems remain safe and reliable. Recording data carefully allows future comparison, trend tracking, and early fault detection before insulation failure occurs.

Acceptable Resistance Values

Technicians measure insulation resistance values in megaohms (MΩ) using a megger tester. New or well-maintained cables usually show readings above 100 MΩ, while in-service cables can remain acceptable above 1 MΩ, depending on voltage rating and insulation type.

Resistance changes with temperature and humidity. Results should be corrected to a standard temperature, usually 20°C, since resistance roughly halves for every 10°C rise. Ambient conditions and cable length should also be noted.

To evaluate long-term insulation quality, some tests include the polarisation index (PI). This ratio compares the 10-minute resistance reading to the 1-minute reading. A PI value above 2.0 indicates good insulation, while a value below 1.0 suggests moisture or contamination. Recording both resistance and PI offers a clearer picture of insulation health.

A simple record table helps maintain clarity:

ParameterExample ValueNotes
Test Voltage1000 V DCBased on cable rating
1-Min Reading80 MΩUsed for PI
10-Min Reading180 MΩUsed for PI
PI (10/1)2.25Good insulation

Identifying Low Readings or Insulation Faults

Low insulation resistance values often point to problems such as moisture ingress, surface contamination, or ageing insulation. A reading below 1 MΩ usually means the insulation is unsafe and needs repair or replacement.

When low readings appear, technicians should first confirm the cable is clean and dry. Dirt or moisture on terminals can cause false results. Retesting after cleaning or drying helps verify if the issue is real.

If results remain low, further inspection is needed. Signs of insulation faults include inconsistent readings between conductors, unstable values during testing, or a polarisation index below 1.5. These conditions indicate trapped moisture or deteriorated insulation layers.

All readings, both normal and abnormal, should be logged with date, temperature, humidity, and cable identification. Consistent documentation supports maintenance planning and helps detect insulation degradation over time.

Common Issues and Fixes

Accurate insulation resistance testing depends on clean surfaces, intact insulation, and correct retesting after any repair. Contamination, damage, or skipped verification steps can lead to false readings, current leakage, or unexpected electrical failures.

Moisture or Dirt on Terminations

Moisture, dust, or oil on cable ends can lower insulation resistance and cause leakage currents. These contaminants create partial conductive paths that distort readings and may hide real insulation degradation.

Technicians should clean and dry all terminations before testing. Use lint-free cloths and ensure the area is free from condensation. If humidity is high, allow the cable to stabilise in a dry environment or apply gentle heat to remove moisture.

After cleaning, measure again. If the resistance increases significantly, contamination was the likely cause. Keeping terminations sealed and protected from dust or water during storage and installation prevents most of these issues.

Problem SourceTypical EffectRecommended Action
MoistureLow readings, unstable valuesDry cable, retest after stabilising
Dirt or greaseSurface leakageClean with solvent, recheck insulation

Damaged Insulation or Joints

Cuts, cracks, or poor joints often cause direct current leakage between conductors or to ground. These defects may result from bending, ageing, or improper cable termination. Even small breaks can produce low resistance readings and early electrical failures.

Inspect all visible insulation and joints carefully. Look for burn marks, swelling, or exposed conductors. Use a continuity test to confirm conductor integrity before repeating the insulation resistance test.

If damage is confirmed, replace or re-terminate the affected section. Applying temporary tape or sealant is not reliable for long-term service. Proper jointing materials and mechanical protection reduce the chance of future degradation.

Re-Testing After Repair

After cleaning or repair, the cable must be retested to confirm insulation recovery. This step ensures that leakage currents have been eliminated and the insulation now meets acceptable resistance levels.

Perform the same test voltage and duration as the original measurement. Compare the new results with previous data. A stable reading above the minimum standard (for example, greater than 1 MΩ for in-service cables) indicates successful restoration.

If readings remain low, the problem may persist deeper within the insulation or at hidden joints. In that case, isolate each section and test separately to locate the fault. Retesting under controlled temperature and humidity gives the most reliable results.

Good Practice for Future Tests

Consistent insulation resistance testing helps maintain cable reliability and prevents electrical faults. Good record-keeping and scheduled testing support both preventive and predictive maintenance, ensuring faults are detected before they cause equipment failure or downtime.

Regular Testing and Maintenance

Technicians should schedule insulation resistance tests at regular intervals based on equipment type, voltage level, and environmental conditions. Cables in humid or dusty areas may need more frequent checks due to faster insulation deterioration.

A preventive maintenance plan should include visual inspection, cleaning of terminals, and re-testing after repairs or modifications. This approach keeps insulation values stable and helps identify gradual changes that may indicate moisture ingress or ageing.

Predictive maintenance uses data trends to forecast when insulation may fail. Comparing new readings to past results helps detect small resistance drops early. This reduces unexpected outages and improves equipment reliability.

The table below gives a sample testing frequency guideline:

Cable TypeVoltage LevelRecommended Test Interval
Low Voltage≤1 kVEvery 12 months
Medium Voltage1–33 kVEvery 6 months
High Voltage>33 kVEvery 3–6 months

Storing Results for Compliance Records

Accurate documentation of test results is essential for safety audits and regulatory compliance. Each record should include the test date, cable identification, applied voltage, insulation resistance value, temperature, and operator name.

Digital logs or maintenance software make it easier to track long-term performance. Storing results in electronic format allows trend analysis and quick access during inspections or fault investigations.

When results are stored properly, engineers can identify patterns that support predictive maintenance strategies. Historical data helps confirm whether insulation degradation is gradual or sudden, guiding decisions on repair or replacement before failure occurs.

Frequently Asked Questions

How do you test the insulation resistance of a cable using a megger?

Technicians disconnect the cable from both ends and discharge any stored charge. They set the megger to the correct test voltage, usually based on the cable’s rated voltage. The red lead connects to the conductor, and the black lead connects to earth or the cable shield. After pressing the test button, they record the steady resistance reading in megaohms.

How do you check for cable faults with a megger?

A megger helps locate insulation faults by comparing readings between conductors and between each conductor and earth. A very low resistance value indicates damaged insulation or moisture ingress. Consistent readings across all phases suggest the cable is in good condition.

What is a good megger reading for cable?

A healthy cable usually shows a reading in the range of hundreds of megaohms to several gigaohms, depending on voltage class and cable type. New or well-maintained cables often exceed 100 MΩ. Readings that drop significantly below expected values may indicate insulation deterioration or contamination.

What is the rule of thumb for the megger test?

A common rule of thumb states that insulation resistance should be at least 1 MΩ per kilovolt of operating voltage, with a minimum of 1 MΩ for low-voltage systems. However, higher values are preferred for critical or high-voltage equipment.

What are the common megger test mistakes?

Frequent errors include testing energised circuits, skipping the discharge step, using the wrong test voltage, or failing to isolate both ends of the cable. Poor lead connections and humid conditions can also distort readings. Careful preparation and adherence to safety protocols reduce these issues.

What is the minimum insulation resistance of a cable?

Standards often specify 1 MΩ as the minimum acceptable value for low-voltage cables. For medium- and high-voltage systems, the minimum may increase to 100 MΩ or more. The exact threshold depends on the cable’s design, voltage rating, and environmental conditions.

What is the acceptable resistance of a cable?

Acceptable resistance varies by cable type and application. Power cables should maintain high insulation resistance, typically above 100 MΩ, to prevent leakage. Control and communication cables may have lower acceptable values but must still meet manufacturer or regulatory standards to ensure safe operation.